SGC DSP Manual do Utilizador Página 18

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 52
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 17
18 Smart Grid Conference 2014 (SGC’14) - Grid Renovation Workshop
Example: Distribution Grid Volt/Var Effect on
Available DR
Use Case
Feeder Voltage: 13.8 kV
Feeder Base Load: 9 MW with Unity Power Factor: 3 MW Constant
Impedance (Z); 3 MW Constant Current (I); 3 MW Constant Power (P)
Participating DR: 900 kW with 0.8 Lag Power Factor
Remaining load after deployment of DR: 8,100 kW with Lead Power
Factor
Feeder Voltage Increase due to Lead Power Factor: 1.5%
Increase in base load due to voltage increase: 135 kW
Net Demand Reduction: 900-135 = 765 kW
Voltage
Increase (%)
Z Load I Load P Load Total
1.5% 3% 1.5% 0%
90 kW 45 kW - 135 KW
Vista de página 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 51 52

Comentários a estes Manuais

Sem comentários